12V-40AH

Maintenance Free 12V / 40AH

Description

12V40AH

Maintenance Free 12V / 40AH

The battery is constructed by plates,separators,safety valves and container. Since the electrolyte is held by a glassmat separator and plates,the battery can use in any direction and position without leakage. 

 Outer Dimensions40AHDimensions and WeightLength ( mm / inch )……………………….……..…196 / 7.72Width ( mm / inch ) ………………………………….166 / 6.54

Height ( mm / inch ) …………………..……….……175 / 6.89

Total Height ( mm / inch )………………………..…175 / 6.89

Approx.Weight( Kg / lbs )……………………… 13.30 / 29.26

  Performance CharacteristicsNominal Voltage ……………………..…………………… 12VNumber of cell ……………………………..……………… 6

Design Life …………………………………..……………. 8years

Nominal Capacity 77°F(25°C)

20 hour rate(2.0A,10.5V) …………………….…………… 40Ah

10 hour rate(3.72A,10.5V) ……………….….…….…..….37.2Ah

5 hour rate (6.82A,10.5V) ……………………..……..…….34.1Ah

1 hour rate(26.0A,9.6V) …………………..…..…..………. 26.0Ah

Internal Resistance

Fully Charged battery 77°F(25°C) ………….…..…….….6mΩ

Self-Discharge

3% of capacity declined per month at 20°C(average)

Operation Temperature Range

Discharge ……………………………………..…………. -20~60°C

Charge ………………………………………..………….. -10~60°C

Storage …………………………………………………… -20~60°C

Max.Discharge Current 77°F(25°C) ……………………. 400A(5s)

Short Circuit Current …………………………………….. 1200A

Charge Methods:Constant Voltage Charge 77°F(25°C)

Cycle use …………………………………………..………14.5-15.0V

Maximum charging current ……………………….…..…..12.0A

Temperature compensation …………………………..…. -30mV/°C

Standby use ………………………………………..………13.4-13.8V

Temperature compensation ………………….…….…..…-20mV/°C

Battery Constructionn

COMPONENT Positive plate Negative plate Container Cover Safety valve Terminal Separator Electrolyte
RAW MATERIAL Lead dioxide Lead ABS ABS Rubber Copper Fiberglass Sulfuric acid

 Charging Methods

Application Charging method Charging Voltageat 25°C Temperature compensation coefficient of charging voltage Max.charging current Charging time25°C(h) Temp(°C)
100% discharge 50% discharge
For standby power source Constant voltage &ConstantCurrentCharging(with current restriction) 13.4-13.8V -20 mV/°C 12.0A 24 20 0~40(32~104°F)
Forcycle service 14.5-15.0V -30 mV/°C 12.0A 16 10

*Temperature compensation of charging voltage is not needed.when using the batteries within 15°C to 35°C range.

200 AH2 copyDischarge Constant Current (Amperes at 77°F25°C)

F.V/Time 5min 10min 15min 30min 45min 1h 2h 3h 5h 8h 10h 20h
9.60V 140 112 80.0 46.0 32.8 26.0 14.0 10.13 6.88 4.53 3.76 2.04
9.90V 136 108 76.0 45.2 32.4 25.8 13.9 10.08 6.84 4.53 3.76 2.04
10.2V 128 100 72.0 44.0 32.0 25.6 13.8 10.00 6.80 4.48 3.73 2.00
10.5V 112 84.0 68.0 41.6 31.6 25.2 13.6 9.88 6.80 4.44 3.73 2.00
10.8V 100 72.0 64.0 36.0 31.2 24.8 13.2 9.60 6.72 4.44 3.64 1.96


Discharge Constant Power (Watts at 77°F25°C)

F.V/Time 5min 10min 15min 30min 45min 1h 2h 3h 5h 8h 10h 20h
9.60V 1530 1224 882 535 374 300 161 117 79.8 52.6 44.0 24.0
9.90V 1464 1176 834 516 370 295 160 116 79.2 52.3 43.7 24.0
10.2V 1398 1104 798 492 365 295 159 116 79.2 52.3 43.7 23.8
10.5V 1224 936 750 463 360 290 157 115 79.2 51.6 43.2 23.3
10.8V 1092 840 708 401 355 286 152 111 78.6 51.6 42.5 22.8