Description
Features
- Three Phase With Neutral
- Smart RS-232 or USB
- Optional SNMP
- Transfer Time:0ms
- CAPACITY:10KVA/8KW-30KVA/24KW
Specification
Specification
MODEL | 10 KVA | 15 KVA | 20 KVA | 30 KVA | |
CAPACITY | 10KVA/8KW | 15KVA/12KW | 20KVA/16KW | 30KVA/24KW | |
INPUT | |||||
Voltage Range | Low Line Loss | 110VAC (Ph-N)±3% at 50% load; 176VAC (Ph-N)±3% at 100% load | |||
Low Line Comeback | Low Line Loss Voltage +10V | ||||
High Line Loss | 300VAC (L-N)±3% at 50% load; 276VAC (L-N)±3% at 100% load | ||||
High Line Comeback | High Line Loss Voltage-10V | ||||
Frequency Range | 46Hz~54Hz @50Hz System; 56Hz~64Hz @60Hz System | ||||
Phase | Three Phase With Neutral | ||||
Power Factor | ≥0.99 at 100% Load | ||||
OUTPUT | |||||
Phase | Three Phase With Neutral | ||||
Output Voltage | 208/220/230/240VAC(Ph-N) | ||||
AC Voltage Regulation | ±1% | ||||
Frequency Range (Synchronized Range) |
46Hz~54Hz @50Hz System; 56Hz~64Hz @60Hz System | ||||
Frequency Range (Batt. Mode) | 50Hz±0.1Hz or 60Hz±0.1Hz | ||||
Overload | AC Mode | 100%~110%: 10min; 100%~130%:1min; >130%:1sec | |||
Battery Mode | 100%~110%: 30sec; 100%~130%:10sec; >130%:1sec | ||||
Current Crest Ratio | 3:1max | ||||
Harmonic Distortion | ≤2% @ 100% Linear Load; ≤5% @ 100% Non-linear Load | ||||
Transfer Time | Line-Battery | 0ms | |||
Inverter-Bypass | 0ms(When phase lock fails,<4ms interruption occurs from inverter to bypass) | ||||
Inverter-ECO | <10ms | ||||
EFFICIENCY | |||||
AC Mode | >89% | >90% | |||
Battery Mode | >86% | >88% | >87% | >89% | |
BATTERY | |||||
Standard Model | Type | 12V/9Ah | |||
Numbers | 20(18-20 adjustable) | 2*20(18-20 adjustable) | 2*20(18-20 adjustable) | 3*20(18-20 adjustable) | |
Recharge Time | 9 hours recover to 90% capacity | ||||
Charging Current | 1.0A±10%(max.) | 2.0A±10%(max.) | 2.0A±10%(max.) | 4.0A±10%(max.) | |
Charging Voltage | 273 VDC±1% | ||||
Long-run Model | Type | Depending on applications | |||
Numbers | 18-20 | ||||
Charging Current | 4.0A ±10%(max.) | 8.0A ±10%(max.) | |||
Charging Voltage | 273 VDC±1% | ||||
PHYSICAL | |||||
Outline | Dimension D*W*H mm |
770*330*850 | 770*330*850 | 770*330*850 | 770*330*1050 |
Net Weight(kgs) | 105 | 150 | 158 | 212 | |
Packaging | Dimension D*W*H mm |
900*463*1100 | 900*463*1100 | 900*463*1100 | 900*463*1080 |
Net Weight(kgs) | 125 | 170 | 178 | 347 | |
ENVIRONMENT | |||||
Operation Temperature | 0~40℃(the battery life will down when >25℃) | ||||
Operation Humidity | <95% and noncondensing | ||||
Operation Altitude | <1000m | ||||
Acoustic Noise Level | Less than 60dB@ 1Meter | Less than 65dB@ 1Meter | |||
MANAGEMENT | |||||
Smart RS-232 or USB | Supports Windows 2000/2003/XP/VISTA/2008, Windows 7,Linux, Unix, and MAC | ||||
Optional SNMP | Power management from SNMP manager and web browser |